How do I choose a fire fighting pump?

How do I know what size fire pump I need?

For example, if you have a 40,000-square-foot building that is all ordinary group 1, the calculation would be 1,500 x 0.15 (density) = 225 + 250 (hose demand) = 475 gpm total for the fire pump. If the structure has multiple hazards, the hazard with the highest gpm calculation dictates the pump size.

What are the key factors that should be considered when selecting a firefighting pump?

You’ll need to know how much water flow and water pressure you’re likely to need, too.

  • Conditions and Regulations. The local conditions are one of the biggest factors to keep in mind. …
  • Water Supply. Knowing about the water supply in your area is also important. …
  • Pressure. …
  • Size and Power. …
  • Mobile Fire Pump.

What is the best pump for fire fighting?

Best Fire Fighting Pumps

# Fire Fighting Pump Our Rating
1. NorthStar High-Pressure Water Pump with Honda GX160 Engine 9/10
2. Koshin SEH-40H Centrifugal Fire Fighting Pump, 1.5″ 8.5/10
3. DuroMax XP702HP 8/10
4. Honda – General Purpose 2-Inch Centrifugal Water Pump 7.5/10
IMPORTANT:  Frequent question: Where are fire extinguisher usually kept?

How do you size a fire jockey pump?

“The pump manufacturer, Armstrong pumps, recommends, as a rule of thumb, to size the jockey for about 1 % of the rated flow of the main fire water pump. Also they recommend that jockey to be sized with 10 psi (0.7 bar) higher pressure than the system design pressure of the firewater ring.”

Is code for fire fighting pumps?

2 REFERENCES

IS No. Title
5120 : 1977 Technical requirements for rotodynamic special purpose pumps (first revision)
6070 : 1983 Code of practice for selection, operation and maintenance of trailer fire pumps, portable pumps, water tenders and motor fire engines (first revision)

How do I choose a pump?

Before you can select a pump that will fit your needs, you must know four things: 1) the total head or pressure against which it must operate, 2) the desired flow rate, 3) the suction lift, and 4) characteristics of the fluid.

What is the maximum allowed suction head for the fire pump?

The maximum actual suction lift for a centrifugal pump is approximately 15 ft when pumping water from an open air tank.

What is PSI in fire fighting?

PSI stands for pressure per square inch, and GPM stands for gallons per minute. Both of these are vital in helping you choose what kind of firefighting pump you need, and it is very important to know about the PSI and GPM before buying any pump, regardless of the use.

Is jockey pump required?

A jockey pump is not required on systems utilizing a fire pump, however, due to their relative simplicity, jockey pumps are the most common method used to maintain system pressure. Since jockey pumps are not required to be listed, any pump capable of producing necessary pressure is acceptable.

IMPORTANT:  How much horsepower does a firetruck have?

How often does a jockey pump run?

The jockey pump starts every 30 minutes or so when the pressure drops from 200 PSI to 150 PSI. It only runs for one second.

What is jockey pump and fire pump?

A jockey pump is a small pump connected to a fire sprinkler system and is intended to maintain pressure in a fire protection piping system to an artificially high level so that the operation of a single fire sprinkler will cause a pressure drop which will be sensed by the fire pump automatic controller, causing the …